Automatic Transfer Switch

OKURA INTEX CO., LTD.

2-19-3-503, Higashi-Gotanda Shinagawaku ,Tokyo 141-0022 ,Japan

Tel:81-3-3445-3988 Fax: 81-3-3445-6657

E-mail okuraintex@aol.com                                                   

 

Automatic Transfer switch : MAC=DT

Reference standard: JEM1038, Transfer time(tripping and closing time) is under 0.3 sec. but give operating command over 0.5 sec. for sure operation

Y2 Type AC250V/DC125V, 30-400A with pausing function, saving power, one-cil operation, common circuit for AC and DC operation, timer connection terminal, high safety design

  width="592" height="234">   

MODEL RATING 3-POLE 3-POLE 4-POLE 4-POLE
 203Y2 250V  30A FRONT BEHIND FRONT BEHIND
 205Y2 250V  50A FRONT BEHIND FRONT BEHIND
 207Y2 250V  70A FRONT BEHIND FRONT BEHIND
 21Y2 250V 100A FRONT BEHIND FRONT BEHIND
 215Y2 250V 150A FRONT BEHIND FRONT BEHIND
 22Y2 250V 200A FRONT BEHIND FRONT BEHIND
 23Y2 250V 300A FRONT BEHIND FRONT BEHIND
 24Y2 250V 400A FRONT BEHIND   -  -

 

 W2 type : AC600V/DC125V, 60-400A, one-coil operation, saving power, common cicuit for AC and DC operation, high safety design

  

TYPE RATING 3-POLE 3-POLE 4-POLE 4-POLE
606W2 600V 60A FRONT BEHIND FRONT BEHIND
61W2 600V 100A FRONT BEHIND FRONT BEHIND
62W2 600V 200A FRONT BEHIND FRONT BEHIND
64W2 600V 400A FRONT BEHIND FRONT BEHIND

 

WN2 type : AC600V/DC125V for 100-1600A, AC600V for 2000-5000A with free-time-neutral(OFF) position to prevent mixture of power source voltage and voltage of load side, double thrrow with two separate contacts, current-breaking characteristics

   

Model NBR RATING 3-POLE 3-POLE 4-POLE 4-POLE
61WN2 600V 100A FRONT - FRONT -
62WN2 600V 200A FRONT - FRONT -
64WN2 600V 400A FRONT - FRONT -
66WN2 600V 600A FRONT BEHIND FRONT BEHIND
68WNA2 600V 800A FRONT BEHIND FRONT BEHIND
610WN2 600V 1000A FRONT BEHIND FRONT BEHIND
612WNA2 600V 1200A FRONT BEHIND FRONT BEHIND
616WN2 600V 1600A FRONT BEHIND FRONT BEHIND
620WN2 600V 2000A - BEHIND - BEHIND
630WN2 600V 3000A - BEHIND - BEHIND
640WN2 600V 4000A - BEHIND - -
650WN2 600V 5000A - BEHIND - -

-: Not available, Rating: rated current, NBR of pole: 3 or 4 pole, Connection: Front or Behind(bcak)

 

CATALOGUE (PLEASE CLICK ---- PORTION)

APPLICATION AND SELECTION

FOR MODEL Y2 EXPLANATION 1), 2) , 3), 4), DIMENTIONS OF Y2MODEL: 5), 6), 7), 8)

FOR MODEL W2 EXPLANATION 1), 2), 3), DIMENTONS OF W2 MODEL : 4), 5) , 6)

FOR MODEL WN2 EXPLANATION 1), 2), 3), 4), 5), 6), 7), DIMENTION OF WN2 MODEL : 8), 9), 10), 11)

REMARKS FOR INSTALLATION

 

 

 

 

 

 

  

 

 

 